Page Content
4 POLE UTILISATION CATEGORY AC23A RATED OPERATIONAL:
CURRENT (IE) 32A
VOLTAGE (UE) 240V/415V 50/60 HZ
POWER 11 KW
STANDARD CARTON QUANTITY : 1
TERMINAL CAPACITY:
16mm2 (Rigid stranded cable)
CONDUIT ENTRY:
2 x 25mm cable entry top and bottom.
Supplied with 2 x 25mm conduit adaptors.
4 x 20mm, 2 x 25mm knockouts for rear cable entry.
BS EN 60947-3:2009
M4413 ENCLOSURES ARE POLYCARBONATE.
Polycarbonate enclosures provide extremely high levels of
impact resistance.Some chemicals and synthetic oils can harm polycarbonate.Call technical hotline for further information.